EP Series 10-60KVA Online UPS 3 Phase

Online UPS manufactured and supplied by SM-VOLTSMART is the most preferred online UPS.

Features
  • Online Double-Conversion
  • DSP Technology Guarantees High Reliability
  • Accept Dual-Mains Input
  • Adjustable Battery Numbers
  • Warranty - 1 Year
Category: Online UPS
Product Description

SM-VOLTSMART, manufactures the Online UPS with PWM technology. The advance IGBT inverter, coupled with an isolation transformer, enhances the reliability and load adaptability. This unique construction for input and output isolation provides the advantages of noise rejection as well as clean and safe neutral line to the load, enables EP UPS to be used with critical load applications.

 

Special Features
  • Online Double-Conversion
  • DSP Technology Guarantees High Reliability
  • True Inbuilt Galvanic Isolation Transformer Design
  • Control Designed to Withstand all kinds of Loads
  • Intelligent Battery Management to Prolong Battery Life Cycle
  • Redundant Fan Design and Independent Ventilation Enhances Durable Operation Under Harsh Environment
  • Adjustable Battery Numbers
  • Accept Dual-Mains Input
  • Parallel Operation with up to 4 Units (Option)
  • Variety of Communication Options Available
  • IGBT based charger for smart battery management & improve input power factor

 

Application

Industries, Medical & Healthcare, IT, Networking & Security

Technical Specifications
Capacity 10 KVA, 15 KVA, 20 KVA, 30 KVA, 40 KVA, 60 KVA
Input Rated AC Voltage 380V / 400V / 415V AC (3Ph+N+PE)
Input Voltage Range 290V ~ 480V AC ± 5V
Input Frequency Range 50 / 60 Hz ± 10% Auto Sensing
Power Factor 0.99
Walk-in Time 5 ~ 300 Sec. (Configurable)
Bypass Rated Voltage 380V / 400V / 415V AC (3Ph+N+PE)
Bypass Voltage Range + 20%, -30% (Configurable)
Bypass Frequency Range 50 / 60 Hz ± 10% (Configurable)
Battery Voltage 384V DC Standard (348 ~ 384 Configurable)
Ripple 1%
Charging Current Max. (A) 0.10C to 0.25C upto 100~300Ah at 100% Load (Configurable)
Output Rated Voltage 380V / 400V / 415V AC (3Ph+N)
Output Frequency Range Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz Battery Mode
Voltage Regulation ±1%
Harmonic Distortion (THDv) 1% Linear Load, 5% Non-Linear Load
Crest Factor / Transfer Time 3:1 / Zero
Efficiency Up to 95% Dual Conversion Mode, 99% ECO Mode
Overload 125% for 10 Min, 􀀀 150% for 1 Min, 􀀀 150% for 300 ms
Parallel Up to 6 Units (Optional)
Display LCD + LED
IP Rating IP 20
Alarm / Protection Short Circuit, Input Under/Over Voltage, Over Temperature, Over Current, Over Load, DC BUS Under / Over Voltage and Battery low
Audible Alarms Alarm for batt. Low, DC High, Inverter Under/Over Voltage, Overload, Short Circuit, Fan Failure & UPS Fault
LED Indicatios Bypass, Mains, Battery and Fault
LCD Display Information Input Voltage & Freq.; Output Voltage, Current, KVA, KW, Total Power, PF, Load % Per Phase, Load % Total & Freq.; Bypass Voltage & Freq.; Inverter Voltage & Freq.; Battery Voltage, DC Bus Voltage, Charging Current, Discharging Current, Temperature
Temperature Operating: 0~45°C, Storage: -10ºC ~ 55ºC
Humidity / Altitude 0~95% RH Non-condersing / <1500 M
Noise Low Audible Noise Level
Quality ISO 9000, ISO 14001, OHSAS 18001, ISO 27001, RoHS
Safety IEC/EN62040-1
EMC / Performance IEC/EN62040-2; IEC/EN62040-3, Complying to CE
Standard RS-232 / Dry Contact / RS-485
Optional SNMP / ModBus / USB
Monitoring Software NetAgent / Muser4000